| MODEL | DIN120-12 | DIN120-24 | DIN120-48 | DIN240-12 | DIN240-24 | DIN240-48 | |||
| OUTPUT | DC Output | 12V | 24V | 48V | 12V | 24V | 48V | ||
| Rated Current | 0~10A | 0~5A | 0~2.5A | 0~16A | 0~10A | 0~5A | |||
| Ripple and Noise | ≤100mVp-p | ≤100mVp-p | ≤150mVp-p | ≤100mVp-p | ≤100mVp-p | ≤150mVp-p | |||
| Voltage ADJ. Range | 12~14V | 24~28V | 48~55V | 12~14V | 24~28V | 48~53V | |||
| Peak Current | 15A | 7.5A | 3.75A | 24A | 15A | 7.5A | |||
| Voltage Accuracy | ≤±2% | ≤±1% | ≤±2% | ≤±1% | |||||
| Line Regulation | ≤±1% | ||||||||
| Load Regulation | ≤±2% | ||||||||
| Set-up Time | ≤2S( 115Vac&230Vac; full load) | ||||||||
| Hold up Time | ≥20mS (115/230Vac input; full load) | ||||||||
| Temperature Coefficient | ≤±0.02%/℃ | ||||||||
| INPUT | Voltage Range | 90~264Vac | |||||||
| Frequency Range | 47Hz~63Hz | ||||||||
| Power Factor @25℃ | ≥0.95 @ 100~230Vac (at full load) | ||||||||
| Efficiency ( Typical) | 12V | 24V | 48V | 12V | 24V | 48V | |||
| ≥90.5% | ≥92.5% | ≥90.5%         ≥92.5% | |||||||
| 25℃ @ 220V, full load | |||||||||
| AC Current (max.) | <1.2A@ 110Vac (at full load) | <2.8A@ 110Vac (at full load) | |||||||
| Inrush Current (Typical) | <35A@115Vac,<70A @ 230Vac;25℃ | ||||||||
| Stand-by Power Consumption | <5W | ||||||||
| PROTECTION | Over current | 110%~150%@Io | |||||||
| Protection type: Hiccup mode; auto recovery | |||||||||
| Over voltage | 120%~150%@Vo | ||||||||
| Shutdown O/Pvoltage.re-power on to recover | |||||||||
| Over temperature | The power supply comes into protection mode when the temperature is greater than 105 °C | ||||||||
| Short Circuit | Long-term mode, auto recovery | ||||||||
| ENVIRONMENT | Operating amb. Temp. & Hum. | -40℃~70℃; 20%~90%RH No condensing (refer to derating curve) | |||||||
| Storage Temp. & Hum. | -40℃~85℃; 10%~95%RH No condensing | ||||||||
| Vibration | 9-200Hz, 10m/s2; 3.5min./1cycle, 5 periods, each along x, y, z axes | ||||||||
| Impulse | 250m/s2, 6ms; 3 times, each along x, y, z axes | ||||||||
| Altitude | 5000m | ||||||||